FDS OBST vs GEOM: accuracy, run time and scalability on four test cases (FDS 6.10.1)

Published by Ruggero Poletto on

GEOM vs OBST gas temperature, Lattimer 35ยฐ wall

TL;DR

  • Walls aligned with the grid: use OBST. GEOM puts the wall exactly in place but takes about 4ร— the wall time; our OBST walls were deliberately placed 1/3 of a cell off the grid, and the error that causes disappears when the wall sits on a cell face.
  • Tilted walls in laminar flow (channel at 14ยฐ, 27ยฐ, 45ยฐ): with default settings GEOM was not more accurate than the OBST staircase: โˆ’1.7 %, โˆ’4.4 % and โˆ’4.8 % flow-rate error at 40 cells across the channel vs โˆ’1.4 %, โˆ’1.6 % and +2.3 % for OBST. GEOM with CCVOL_LINK=0 gets +3.0 % at 20 cells but needs 17ร— more time steps.
  • Sphere wake at 20 cells per diameter: GEOM gets the drag right at Re 100 (Cd 1.084 vs 1.087) and +13 % at Re 200; the OBST staircase reports Cd about a third low, while both put the wake length within 3โ€“10 % of Johnson & Patel.
  • Lattimer tilted wall (fire): GEOM gives smooth, repeatable gauge profiles that match the official NIST FDS 6.11.1 results within 19 %, at 3.5โ€“4.0ร— the wall time of OBST. OBST point gauges on the staircase jump by up to 10ร— between neighbouring gauges depending on which step face they land on. Both under-predict the experiment on tilted walls (first gauge at 35ยฐ: 23 kW/mยฒ vs 55 measured).
  • Cost and scaling: on the same 1.58 M-cell grid a GEOM time step costs 4.6โ€“9.9ร— more than an OBST step, because GEOM switches FDS from the FFT pressure solver to the ULMAT/PARDISO matrix solver and the pressure solve then takes 42โ€“66 % of the compute time (MPI wait excluded). GEOM also gains more from extra meshes (12.8ร— faster from 8 to 64 meshes vs 6.0ร— for OBST), because the matrix solve gets much cheaper as each mesh gets smaller.

All runs: FDS 6.10.1 (FDS-6.10.1-0-g12efa16-release) on cloudHPC hypercore spot instances, November 2026.

Why compare OBST and GEOM now

FDS has always described solid objects with &OBST: boxes aligned with the grid. A sloped roof, a tilted wall or a cylinder becomes a staircase of cells. Since FDS 6.7 the cut-cell immersed boundary method (&GEOM, CC_IBM) lets you put an arbitrary triangulated surface in the grid: FDS cuts the cells, keeps the true wall position and orientation, and links very small cut cells to their neighbours so the time step does not collapse.

On cloudHPC we see more and more GEOM inputs: terrain from qgis2fds, rotated fans (our jet fan post), imported CAD. The question users ask us is always the same: is GEOM worth the extra run time, and how much extra is it? Answers in forums are mostly anecdotal, so we ran the same physics with both descriptions on four cases where there is an exact answer or an experiment:

  1. Laminar Poiseuille flow in a tilted channel โ€“ exact solution, 4 angles ร— 4 grids.
  2. Flow past a sphere at Re 100 and 200 โ€“ drag correlation and measured wake length.
  3. Lattimer tilted wall โ€“ a fire against a wall tilted 0โ€“67ยฐ from vertical, from the NIST FDS validation suite.
  4. Strong scaling โ€“ the Lattimer 35ยฐ wall at 1.25 cm on 8, 16, 32 and 64 meshes.

The FDS version is the same as the middle version of our FDS 6.9.1 vs 6.10.1 vs 6.11.1 comparison.

Results at a glance

Case Metric Reference GEOM OBST Verdict
Channel 0ยฐ, 40 cells flow-rate error exact +0.12 % +6.2 % (wall snapped 1.2 cm) GEOM, or OBST on cell faces
Channel 27ยฐ, 40 cells flow-rate error exact โˆ’4.4 % โˆ’1.6 % OBST
Channel 45ยฐ, 40 cells flow-rate error exact โˆ’4.8 % +2.3 % OBST
Channel 27ยฐ, 20 cells flow-rate error exact โˆ’8.6 % (default) / +3.0 % (CCVOL_LINK=0, 17ร— steps) โˆ’5.7 % depends on budget
Sphere Re 100, D/20 Cd 1.087 1.084 0.722 GEOM
Sphere Re 200, D/20 Cd 0.776 0.876 0.517 GEOM (closer)
Sphere Re 100 / 200 wake length L/D 0.887 / 1.461 0.977 / 1.602 0.916 / 1.525 OBST (closer)
Lattimer 35ยฐ, 2.5 cm heat flux, first 3 gauges 55.3 / 28.0 / 13.7 kW/mยฒ 23.0 / 10.9 / 5.2 9.5 / 10.1 / 1.7 (point gauges) GEOM (OBST point gauges unreliable)
Lattimer, all angles, 2.5 cm wall time on 4 cores โ€“ 2.3โ€“2.4 h 36โ€“40 min OBST 3.5โ€“4.0ร— faster
Scaling, 1.58 M cells s per step, 8 โ†’ 64 meshes โ€“ 4.92 โ†’ 0.384 0.499 โ†’ 0.083 OBST 4.6โ€“9.9ร— cheaper

How the runs were set up

  • Solver: FDS 6.10.1, the cloudHPC fds6.10.1 app, one MPI process per &MESH (except the sphere: 60 meshes grouped on 16 processes with MPI_PROCESS).
  • Instances: hypercore (physical cores) on spot, DT_RESTART on the long runs. The 64-mesh scaling runs used a 96-vCPU machine because 64-vCPU hypercore spot was not available that day.
  • GEOM: default settings of 6.10.1 unless noted (cut-cell volume linking on). With GEOM in the input FDS 6.10.1 switches the pressure solver from FFT to ULMAT with MKL PARDISO (printed in the .out file); the OBST runs used FFT.
  • OBST: the staircase was built from the same surface: a cell is solid when its centre lies inside the body. Same grid, same physics, same output in both.
  • Same input otherwise: every OBST/GEOM pair differs only in the solid description (and, for the tilted wall, the gauge orientation, see Case 3).

Case 1 โ€“ Poiseuille flow in a tilted channel

Sketch of case 1

Setup. A periodic box contains a fluid layer of height H = 0.6 m between two solid slabs. The channel is tilted 0ยฐ, 14.04ยฐ (slope 1:4), 26.57ยฐ (1:2) or 45ยฐ to the grid; the box size follows the angle (Lx = P/sin ฮธ, Lz = P/cos ฮธ, P = 1 m) so the geometry is exactly periodic. A body force F = 1 N/mยณ (&WIND FORCE_VECTOR, a force per unit volume) drives the flow along the channel; ฮผ = 0.025 kg/(mยทs), DNS mode, no gravity. The exact solution is the plane Poiseuille profile: flow rate per unit width q = F Hยณ/(12 ฮผ) = 0.72 mยฒ/s and centreline velocity u_c = F Hยฒ/(8 ฮผ) = 1.8 m/s (Re โ‰ˆ 35). We ran 10, 20, 40 and 80 cells across H. Flow rate is measured with an AREA INTEGRAL of velocity across the channel, taken at the end of the run (20โ€“30 s of flow time); in the finished runs it had been steady to within 0.1 % since 12โ€“15 s, except the coarsest 45ยฐ GEOM case (10 cells), which was still drifting slowly (โˆ’13.5 % at 10 s, โˆ’14.3 % at 20 s).

Results โ€“ flow-rate error vs exact (%)

Angle Cells across H GEOM OBST
0ยฐ 10 +1.78 +27.49
0ยฐ 20 โˆ’0.27 +3.58
0ยฐ 40 +0.12 +6.21
0ยฐ 80 โ€“ +0.78
14ยฐ 10 โˆ’3.94 โˆ’5.90
14ยฐ 20 โˆ’2.85 โˆ’2.62
14ยฐ 40 โˆ’1.74* โˆ’1.44
14ยฐ 80 โ€“ โˆ’0.95*
27ยฐ 10 โˆ’6.95 โˆ’3.23
27ยฐ 20 โˆ’8.64 (CCVOL_LINK=0: +2.98) โˆ’5.74
27ยฐ 40 โˆ’4.36 โˆ’1.63
27ยฐ 80 โ€“ โˆ’0.51*
45ยฐ 10 โˆ’14.29 โˆ’2.52
45ยฐ 20 โˆ’6.13 +6.36
45ยฐ 40 โˆ’4.78 +2.29
45ยฐ 80 โ€“ โˆ’0.19*

* Run stopped early to save time (T_END 20 s): 14ยฐ GEOM 40 cells at 15.7 s, 27ยฐ and 45ยฐ OBST 80 cells at 11.7 s and 15.3 s, 14ยฐ OBST 80 cells at 9.7 s. The steady flow rate is extrapolated from the start-up transient with an exponential fit, q(t) = qโˆž(1 โˆ’ bยทe^(โˆ’t/ฯ„)). Tested on all eight finished 40- and 80-cell runs, fitting only the first 6.7 s reproduces their final flow rate within 0.02 %.

Channel flow-rate error vs grid

What we learned.

  • Aligned walls: GEOM puts the wall exactly where it is and is within 0.3 % from 20 cells. OBST errors at 0ยฐ jump around (+27 %, +3.6 %, +6.2 %, +0.8 %) because the walls were placed 1/3 of a cell off the grid on purpose: the staircase snaps each wall to a cell face, and since q โˆ Hยณ a 2 % change of H is a 6 % error. At 40 cells the OBST channel is 0.612 m wide instead of 0.600 m, which predicts +6.1 %, against the +6.2 % we measured. Put your OBST walls on cell faces and this error disappears.
  • Tilted walls: the staircase is surprisingly good. Its errors change sign and converge, though not monotonically: โ‰ค 2.3 % at 40 cells and โ‰ค 1 % at 80 cells (โˆ’0.95 %, โˆ’0.51 %, โˆ’0.19 %). On tilted walls, GEOM with default settings under-predicts the flow at every angle and every grid (โˆ’1.7 % to โˆ’14.3 %) and converges slowly: โˆ’1.7 %, โˆ’4.4 % and โˆ’4.8 % at 40 cells. The likely cause is cut-cell linking, which merges small cut cells into their neighbours and adds wall drag: switching it off (CCVOL_LINK=0 on &MISC) moved the 27ยฐ/20-cell result from โˆ’8.6 % to +3.0 %.
  • But without linking the small cut cells set the time step: 318,024 steps vs 18,612 for the same 30 s, 17ร— more, and 6,724 s vs 370 s of wall time. That is not a setting for production runs.
  • Cost: on the same grid GEOM needs 1.5โ€“4.0ร— more time steps per simulated second and about twice the CPU time per cell and step (4.5โ€“7.9 ยตs vs 2.3โ€“3.7 ยตs on one core; one OBST run reached 7.6 ยตs, probably on a slower spot machine).

Time steps per simulated second, GEOM vs OBST

Case 2 โ€“ Flow past a sphere at Re 100 and 200

Sketch of case 2

Setup. We started from the NIST verification inputs geom_sphere_Re100_40D.fds and geom_sphere_Re200_40D.fds (Bluff_Body_Flows): a sphere of diameter D = 1 m in a uniform stream, DNS, with a fine block of meshes around the sphere and coarser meshes outside. We ran them at 20 cells per diameter (60 meshes, 594,864 cells, 16 MPI processes) instead of 40: the 40-cell GEOM sizing run took 5.07 s per time step against 0.42 s for OBST, with a time step 2.4ร— smaller, and we dropped it (see “What didn’t work”). The OBST sphere is the voxel version of the same sphere (cell centres inside r = 0.5 m). Drag is the time average of the FDS pressure and viscous force devices over the last 10 s; the wake length comes from the time-averaged centreline velocity. References: Cd from the Clift, Grace & Weber correlation (1.087 at Re 100, 0.776 at Re 200) and the recirculation length measured by Johnson & Patel (1999): L/D = 0.887 and 1.461.

Results

Case Cd Cd error pressure / viscous Cd Wake L/D L/D error Wall time
Re 100 GEOM 1.084 โˆ’0.3 % 0.632 / 0.452 0.977 +10 % 2,377 s
Re 100 OBST 0.722 โˆ’34 % 0.519 / 0.204 0.916 +3.3 % 566 s
Re 200 GEOM 0.876 +13 % 0.600 / 0.276 1.602 +9.6 % 2,167 s
Re 200 OBST 0.517 โˆ’33 % 0.411 / 0.106 1.525 +4.4 % 773 s

Sphere wake, GEOM vs OBST

What we learned.

  • Forces on a curved body: use GEOM. The GEOM drag is spot on at Re 100. At Re 200 it is 13 % high at 20 cells per diameter; the NIST case uses 40.
  • Do not trust force devices on a staircase sphere. The OBST viscous drag is less than half of GEOM’s and the total is a third too low. The flow around the voxel sphere is not that wrong โ€“ its wake is as long as the measured one โ€“ but the integrated wall forces on the step faces are.
  • The OBST wake length is actually closer to the experiment than GEOM’s at this resolution. A blocky sphere is a slightly bigger sphere, and that helps here by luck, not by design.
  • Cost: GEOM took 2.8โ€“4.2ร— the wall time of OBST on the same 16 processes. The cut-cell meshes around the sphere carry all the extra pressure work while the other ranks wait: in the FDS _cpu.csv file about half of the GEOM run time is MPI wait (COMM), against a quarter for OBST.

Case 3 โ€“ Lattimer tilted wall (fire)

Sketch of case 3

Lattimer tilted wall apparatus, NIST FDS Validation Guide
The tilted-wall apparatus (photo: FDS Validation Guide, NIST, public domain).

Setup. Lattimer and co-workers (Fire Science Solutions / Virginia Tech) burned propane on a 0.3 m square sand burner at the base of a 1.5 m ร— 0.6 m ceramic board tilted 0ยฐ, 11ยฐ, 23ยฐ, 35ยฐ, 49ยฐ and 67ยฐ from vertical, and measured gauge heat flux and temperature at 9 points every 0.15 m along the centreline. We used the 50 kW tests and the NIST validation input Lattimer_Tilted_Wall (TIME_SHRINK_FACTOR=10: 300 s of FDS time = 30 s of real gas time; averages over the last 15 s). 2.5 cm grid, 4 meshes, 197,120 cells, 4 MPI processes. The NIST input uses GEOM; for OBST we built the staircase of the 2.5 cm-thick board and moved each gauge to the nearest exposed face of the staircase. We also ran OBST at 1.25 cm (1.58 M cells, 32 meshes) for 35ยฐ and 67ยฐ, and we compare with the official NIST GEOM results of FDS 6.11.1 (firemodels/out).

Results โ€“ gauge heat flux, kW/mยฒ (gauges 1โ€“3, first at 0.15 m above the burner edge)

Angle Experiment GEOM 6.10.1 OBST 2.5 cm (point) OBST riser face NIST GEOM 6.11.1 OBST 1.25 cm
0ยฐ 66.1 / 46.8 / 33.2 43.0 / 34.6 / 27.6 41.9 / 36.0 / 29.2 โ€“ 38.8 / 32.0 / 26.9 โ€“
11ยฐ 65.7 / 44.8 / 28.6 39.8 / 28.3 / 17.2 44.6 / 32.7 / 7.4 44.2 / 32.8 / 20.3 35.1 / 26.4 / 17.6 โ€“
23ยฐ 59.7 / 35.9 / 22.2 30.5 / 17.4 / 9.0 31.7 / 7.4 / 9.2 32.0 / 14.0 / 9.3 28.9 / 17.8 / 9.6 โ€“
35ยฐ 55.3 / 28.0 / 13.7 23.0 / 10.9 / 5.2 9.5 / 10.1 / 1.7 22.9 / 10.2 / 5.8 22.6 / 11.3 / 5.6 19.6 / 11.2 / 6.3
49ยฐ 44.8 / 15.4 / 7.2 14.9 / 6.3 / 3.1 6.3 / 6.6 / 1.1 17.5 / 6.6 / 4.0 13.2 / 5.8 / 3.1 โ€“
67ยฐ 16.1 / 7.4 / 4.2 6.9 / 2.9 / 1.4 5.2 / 5.5 / 0.7 12.0 / 5.6 / 2.3 6.5 / 2.9 / 1.5 9.5 / 4.9 / 0.7

Lattimer gauge heat flux, all angles

Lattimer 35ยฐ: riser vs tread on the OBST staircase

What we learned.

  • At 0ยฐ there is little difference: the wall is aligned with the grid and OBST and GEOM agree within 6 % on the first three gauges (43.0 / 34.6 / 27.6 vs 41.9 / 36.0 / 29.2 kW/mยฒ).
  • On a staircase wall a “point gauge” is ill-defined. A gauge on a tilted OBST wall sits either on a riser (vertical step face) or on a tread (horizontal step face). On the 35ยฐ wall the riser faces read 2โ€“5ร— the tread faces, so the point-gauge profile jumps by up to 7ร— from one gauge to the next depending on where each gauge landed (up to 10ร— at 49ยฐ). Read on the riser faces, OBST matches the official NIST GEOM results within about 10 % on the first five gauges.
  • Our GEOM runs reproduce the NIST results. FDS 6.10.1 GEOM is within 19 % of the official FDS 6.11.1 output on every gauge at every angle (first gauges within 14 %), so the setup is the validated one.
  • Up to 35ยฐ the right face of the staircase matches GEOM: on the riser faces the first five gauges are within about 30 % of GEOM. At 49ยฐ and 67ยฐ no face does: the risers read 1.1โ€“2.2ร— the GEOM flux on the first five gauges and the treads 0.25โ€“0.75ร—. Gas temperatures near the staircase are even more sensitive: the OBST thermocouple at the first gauge reads 105 ยฐC at 35ยฐ against 426 ยฐC for GEOM (681 ยฐC measured), probably because it sits in the recess of a step, away from the hot boundary layer.
  • Cost: with the same 4 meshes and practically the same number of time steps, GEOM took 2.3โ€“2.4 h per run and OBST 36โ€“40 min (3.5โ€“4.0ร—).
  • Everyone under-predicts the tilted cases. At 35ยฐ the measured flux at the first gauge is 55 kW/mยฒ; NIST’s own GEOM result is 23 kW/mยฒ, ours 23.0. Since the official NIST result shows the same gap, it is a limitation of the model at this resolution, not a question of OBST vs GEOM.
  • Halving the cell size does not rescue OBST. At 1.25 cm the staircase is finer but the zig-zag remains (35ยฐ: 19.6, 11.2, 6.3, then 1.3 kW/mยฒ), and the run cost about 17ร— more than the 2.5 cm one.

What didn’t work

  • GEOM sphere at 40 cells per diameter. The NIST resolution. Our sizing run measured 5.07 s per step for GEOM against 0.42 s for OBST, with a 2.4ร— smaller time step, i.e. ~29ร— the cost of OBST: the full 35 s run would have taken about 18 hours on 96 cores. We stopped it and moved both methods to 20 cells per diameter.
  • Turning off cut-cell linking (CCVOL_LINK=0). It fixes most of the GEOM channel error (โˆ’8.6 % โ†’ +3.0 %) but at 17ร— the time steps. Useful as a check, not in production.
  • Reading OBST wall flux from an “equivalent area”. We first tried to average the boundary file over the staircase area that corresponds to a flat gauge. The result depended on how riser and tread areas were weighted and was not robust, so the post reports the riser and tread values separately.
  • Mesh refinement blocks across the sphere. The first 20-cell sphere stopped at start-up with ERROR(431): a fine mesh boundary at x = 0.35 m did not coincide with a coarse cell face. FDS requires that a coarse cell face never spans two fine meshes; we rebuilt the fine block with 2.7 m long meshes.

Case 4 โ€“ Scalability on the Lattimer wall at 1.25 cm

Setup. The 35ยฐ Lattimer wall at 1.25 cm (1,576,960 cells), split into 8, 16, 32 and 64 equal meshes, one MPI process per mesh, 20 s of FDS time. Time per step averaged from step 100 to the end; hypercore spot, 64 meshes on a 96-vCPU machine. The 16-mesh OBST run was repeated: the two runs gave 0.330 and 0.509 s per step on identical machines, a reminder of the spread you get on cloud spot instances; the chart uses the faster one.

Meshes GEOM s/step OBST s/step GEOM / OBST GEOM wall time OBST wall time
8 4.918 0.499 9.9ร— 5,437 s 534 s
16 2.223 0.330 6.7ร— 2,407 s 354 s
32 1.192 0.200 6.0ร— 1,373 s 217 s
64 0.384 0.083 4.6ร— 406 s 91 s

Strong scaling, GEOM vs OBST

What we learned.

  • GEOM is 4.6โ€“9.9ร— more expensive per step on this grid. Most of it is the pressure solver: PRES (ULMAT/PARDISO) takes 42โ€“66 % of the GEOM compute time against 15โ€“20 % for OBST (FFT), MPI wait excluded.
  • GEOM scales “too well”: 12.8ร— faster from 8 to 64 meshes (160 % parallel efficiency) against 6.0ร— (75 %) for OBST. The reason is the matrix pressure solve: its cost grows faster than the mesh size, so splitting the domain cuts the total pressure work summed over all processes from about 14,300 to 3,900 core-seconds (3.7ร— less) between 8 and 64 meshes.
  • Load balance gets worse, not better: MPI wait grows from 47 % to 64 % of the GEOM run time, and the busiest process spends 2.1ร— (8 meshes) to 3.9ร— (64 meshes) the average time in the pressure solve. OBST waits 10โ€“22 %.
  • Practical rule: if you use GEOM, give it more and smaller meshes than you would give OBST; the extra cores pay for themselves in pressure-solver time. (The 64-mesh runs used a 96-vCPU machine, so the last point also includes a hardware change.)

Run times and costs

Series Runs Instance Wall time per run Cost
Channel, run to T_END (incl. 0ยฐ at 80 cells and CCVOL_LINK=0) 25 2 vCPU hypercore spot 0.4 s โ€“ 1.9 h solver time โ‚ฌ1.86
Channel, stopped early (14ยฐ GEOM 40 cells, OBST 80 cells at 14ยฐ/27ยฐ/45ยฐ) 4 2 vCPU hypercore spot 2.5โ€“4.8 h solver time โ‚ฌ3.14
Sphere, D/20 4 16 vCPU hypercore spot 9โ€“40 min โ‚ฌ3.90
Lattimer 2.5 cm OBST 6 4 vCPU hypercore spot 36โ€“40 min โ‚ฌ2.02
Lattimer 2.5 cm GEOM 6 4 vCPU hypercore spot 2.3โ€“2.4 h โ‚ฌ6.68
Lattimer 1.25 cm OBST 2 32 vCPU hypercore spot ~1.4โ€“1.5 h โ‚ฌ11.34
Scaling GEOM (8โ€“64 meshes) 4 8โ€“96 vCPU hypercore spot 7โ€“91 min โ‚ฌ7.56
Scaling OBST (8โ€“64 meshes, + repeat) 5 8โ€“96 vCPU hypercore spot 1.5โ€“9 min โ‚ฌ3.61
Sizing runs (sphere at 40 and 20 cells/D, Lattimer) 8 4โ€“96 vCPU hypercore spot 7โ€“27 min billed โ‚ฌ8.72
Total โ‚ฌ48.83

How to run these cases on cloudHPC

  1. Take the FDS input of the case you want: the Lattimer and sphere inputs are in the FDS validation and verification suites (references 2โ€“3); the tilted channel is a periodic box with two slabs and a &WIND FORCE_VECTOR, as described in Case 1.
  2. Upload the case folder to your cloudHPC storage and launch it with the fds6.10.1 solver. Choose hypercore with as many vCPU as MPI processes: one per &MESH line, or the number of MPI_PROCESS groups when meshes are grouped (sphere case: 16).
  3. Tips from this work:
    • Spot instances are fine for FDS if &DUMP DT_RESTART is set: cloudHPC restarts the run automatically.
    • Periodic cases with &VENT MB='...' PERIODIC stop cloudHPC from splitting a single mesh automatically: split the mesh yourself if you want more than one process.
    • Mesh refinement blocks must line up: a coarse cell face may not span two fine meshes (ERROR(431)).
    • With GEOM, check the .out file: “Solver: ULMAT with MKL PARDISO” tells you the run uses the matrix pressure solver, and the pressure solve will dominate.
    • TIME_SHRINK_FACTOR makes the progress bar misleading: the log shows “Scaled Simulation Time”.

FAQ

Is GEOM more accurate than OBST in FDS?
For forces on curved bodies (drag on a sphere) yes, clearly. For flow along a tilted wall, not with default settings: in our tilted channel the OBST staircase was within 2.3 % at 40 cells while GEOM was 1.7โ€“4.8 % low. For fire heat flux on a tilted wall GEOM is the safer choice: the OBST result depends on which step face each gauge lands on, while GEOM reproduces the NIST validation results.

How much slower is GEOM than OBST?
1.5โ€“4.0ร— more time steps on the same grid in laminar flow, 2.8โ€“4.2ร— the wall time on the sphere, and 4.6โ€“9.9ร— the cost per step on a 1.58 M-cell fire case. The main cost is the pressure solver: GEOM uses ULMAT/PARDISO instead of FFT.

Does GEOM scale in parallel?
It scales better than OBST in relative terms (12.8ร— from 8 to 64 meshes vs 6.0ร—) because the ULMAT/PARDISO pressure solve gets much cheaper on smaller meshes, even though the load balance gets worse. In absolute terms the 64-mesh GEOM run (0.384 s/step) was only 1.3ร— faster than the 8-mesh OBST run (0.499 s/step) while using 8ร— the cores.

Where should I put a heat flux gauge on a sloped OBST wall?
On a riser (vertical step face, IOR=ยฑ1) the value is close to what a smooth wall gives; on a tread (horizontal face, IOR=ยฑ3) it can be half or less. Check where each device lands, or use a boundary file and read both faces.

What is CCVOL_LINK in FDS?
A &MISC parameter that controls how small cut cells are linked to their neighbours in GEOM. The default linking keeps the time step reasonable; CCVOL_LINK=0 disables it and gave us a more accurate channel flow at 17ร— the time steps.

References

  1. McGrattan K. et al., Fire Dynamics Simulator User’s Guide and Technical Reference Guide, NIST Special Publication 1019/1018, FDS 6.10.1. https://pages.nist.gov/fds-smv/
  2. McGrattan K. et al., Fire Dynamics Simulator Validation Guide, NIST SP 1018-3 โ€“ Lattimer tilted wall. https://pages.nist.gov/fds-smv/
  3. FDS source, verification and validation inputs, tag FDS-6.10.1: https://github.com/firemodels/fds
  4. Experimental data (Lattimer tilted wall, Johnson & Patel sphere): https://github.com/firemodels/exp
  5. Official NIST FDS validation outputs (FDS-6.11.1): https://github.com/firemodels/out
  6. Johnson T.A., Patel V.C. (1999), Flow past a sphere up to a Reynolds number of 300, Journal of Fluid Mechanics 378, 19โ€“70. https://doi.org/10.1017/S0022112098003206
  7. Clift R., Grace J.R., Weber M.E. (1978), Bubbles, Drops, and Particles, Academic Press.
  8. cloudHPC blog, Modelling a jet fan that is not aligned with the FDS grid: louvers vs a rotated GEOM fan: https://cloudhpc.cloud/2026/11/02/fds-jet-fan-not-aligned-with-grid/
  9. cloudHPC blog, FDS version comparison: 6.9.1 vs 6.10.1 vs 6.11.1: https://cloudhpc.cloud/2026/11/01/fds-version-comparison-6-9-6-10-6-11-validation/

CloudHPC is a HPC provider to run engineering simulations on the cloud. CloudHPC provides from 1 to 224 vCPUs for each process in several configuration of HPC infrastructure - both multi-thread and multi-core. Current software ranges includes several CAE, CFD, FEA, FEM software among which OpenFOAM, FDS, Blender and several others.

New users benefit of a FREE trial of 300 vCPU/Hours to be used on the platform in order to test the platform, all each features and verify if it is suitable for their needs