Case 2 setup: displacement-ventilated two-person office (Yuan et al. 1999)

Thermal comfort (ISO 7730) with OpenFOAM: we checked the comfort function object, found a draught-rate bug and fixed it

TL;DR OpenFOAM’s comfort function object computes PMV, PPD and draught rate (DR) per ISO 7730 in every cell. We verified it on cloudHPC with OpenFOAM v2606. PMV and PPD are correct: within 0.003 PMV and 0.08 % PPD of the ISO 7730 Table D.1 examples. DR is not: the turbulence-intensity Read more